MODBUS Configuration:
Comport Setting :
- Baudrate : 9600
- Databits : 8
- Parity : None
- Stopbits : 1
Function Code : 0x06
Use Function 06 : Write Single Register to change below settings.
| Parameter Name | Address | Value |
|---|---|---|
| LED Module Count | 29 | 1-9 (auto save) |
| X Offset | 30 | 0 (must be zero) |
| Protocol | 31 | EA = 0 MODBUS = 1 (auto save) |
| Firmware Version | 32 | - |
| Restart Controller | 33 | - |
| Font Type | 35 | Regular = 0 (single line) Big = 1 (dual line) |
| Brightness | 36 | TBD |
| Baudrate | 37 | *see below |
| Data Bits | 38 | 7 = 7 Data Bits 8 = 8 Data Bits 9 = 9 Data Bits |
| Parity | 39 | 0 = None 1 = Odd 2 = Even |
| Stop Bits | 40 | 1 = 1 Stop Bits 2 = 2 Stop Bits |
| Modbus Device ID | 41 | - (auto save) |
| Save Setting | 42 | 1 |
| Reset Swtich Status | 43 | 0 = switch pressed (read only) |
| Response Time | 44 | 0 (must be zero) |
Baudrate Setting:
0 = 300
1 = 600
2 = 1200
3 = 2400
4 = 4800
5 = 9600
6 = 14400
7 = 19200
8 = 28800
9 = 38400
10 = 56000
11 = 57600
12 = 115200
13 = 128000
14 = 256000
other = 9600
Note : Do not modify any other address value.
Function Code : 0x10
Use Function 16 : Write Multiple Registers to write data on display
Line 1 start adress = 1000
Line 2 start adress = 2000